M - Series

Industrial Combustion M Burner

M series burners are designed for a wide range of applications such as boilers, heaters, furnaces, kilns and dryers. The M series offers natural gas, propane gas, air atomized #2-#6 oil and combination gas/oil fuel options at capacities from 1,400,000 to 10,500,000 MBTU/Hour. Full modulation and cam trim adjustment provides optimum performance to meet load demand.

 

Stock Burners Include:

 

  • MMG #2 Oil - Combination natural gas and air atomized #2 Oil
  • Low-pressure air atomizing system on oil with rotary vane compressor
  • Full Modulation
  • Auto Fuel Changeover
  • Piston-type positive displacement oil metering system
  • Hinged combustion head for easy access and maintenance
  • Backward-curved impeller provides adequate combustion air for various furnace pressures
  • UL & cUL listed
  • Burners ranging in size from MMG 22 - 84 are stocked in Wymbs warehouse ready for immediate delivery (MMG 14 & 105  must be special ordered)

 

Optional Features Include: (Burner must be Special Ordered)

 

  • MG - Natural Gas only, MM - air atomized #2 Oil only, MM - air atomized #4 Oil, MMG - air atomized #4 oil and natural gas, ME - air atomized #6 oil. MEG - air atomized #6 oil and natural gas
  • Siemens ventless gas trains (Fully assembled) in stock and available for delivery with your burner
  • Parallel positioning available for optimal control throughout the firing range (Siemens LMV, Fireye Nexus, Honeywell Links)
  • Cam trim available with 14-point adjustment range for consistent air/fuel ratios
  • Low NOx with FGR capabilities
  • FGR modulating valve
  • Nozzle line electric heater standard on medium to heavy oil burners
  • Many other accessory items including Sequence Draft Control System, Lead Lag System, and Smoke Opacity Monitors
  • Burners can be built to job specifications

 

Capacities and Specifications  (For stock MMG Burners)












*1 Burner voltage is for our in stock burners, please call to order burners with different voltages

*2 MMG 14-30 do not have an "S" or "P" designation

*3 Minimum gas pressure required at train inlet with a 4" Siemens Gas Train, please call us for pressure requirements on smaller Siemens Gas Trains. A gas booster is required for lower pressures than listed above, we can supply you with an Eclipse Gas Booster.

Gas Input (Mbtu/hr)

#2 Oil Input (US gph)

Burner Voltage *1

Boiler Horsepower

Blower Motor Horsepower "S" *2

Blower Motor Horsepower "P"

Furnace Pressure "S" (w.c.) *2

Furnace Pressure "P" (w.c.)

Gas Pressure Required 4" Train ("w.c.) *3

Shipping Weight

14

54

63

42

34

30

28

22

3,150

22.5

230/1/60

75

2

 

0.75

 

1.7"

500

1,400

10

115/1/60

33

1/2

 

0.75

 

2.0"

450

8,400

60

208/3/60

200

5

7-1/2

0.75

2.0

5.1"

1,200

6,300

45

208/3/60

150

3

3

0.75

2.0

6.9"

750

5,600

40

208/3/60

133

2

3

0.75

2.0

5.5"

750

2,200

15.7

115/1/60

52

1/2

 

0.75

 

2.2"

450

2,800

20

230/1/60

67

2

 

0.75

 

1.5"

500

4,200

30

208/3/60

104

2

2

0.75

2.0

2"

650

3,500

25

208/3/60

83

2

2

0.75

2.0

2.2"

650

Burner Size

84

105

10,500

75

208/3/60

250

7-1/2

7-1/2

0.75

2.0

5.6"

1,250